N2XH HALOGEN FREE PVC Wire
|
Code: N2XH
Standards: VDE 276-604
Construction:
1- Solid or Stranded Copper Conductor
2- XLPE insulation(cross-linked PE).
3- Special LSOH Filling
4- Special LSOH Outer Sheath
Application:
Places where there is risk of fire and crowded places like shopping malls, business centers, hotels, schools, tunnels etc.
Technical Data :
Max. operating temperature 90℃
|
Num. of Cores and Nominal Cross Section |
No. of Wires & Diameter |
Thickness of Insulation |
Thickness of Sheath |
Average Overall Diameter |
Approx. Total Weight |
No.×mm2 |
No.×mm |
mm |
mm |
max.mm |
kg/km |
2 × 1.5 |
1.35 |
0.7 |
1.8 |
10.1 |
126 |
2 × 2.5 |
1.73 |
0.7 |
1.8 |
10.9 |
157 |
2 × 4 |
2.19 |
0.7 |
1.8 |
11.8 |
200 |
2 × 6 |
2.68 |
0.7 |
1.8 |
12.8 |
253 |
2 × 10 |
7 × 1.32 |
0.7 |
1.8 |
15.4 |
395 |
2 × 16 |
7 × 1.66 |
0.7 |
1.8 |
17.6 |
558 |
3 × 1.5 |
1.35 |
0.7 |
1.8 |
10.6 |
147 |
3 × 2.5 |
1.73 |
0.7 |
1.8 |
11.5 |
187 |
3 × 4 |
2.19 |
0.7 |
1.8 |
12.4 |
243 |
3 × 6 |
2.68 |
0.7 |
1.8 |
13.5 |
315 |
3 × 10 |
7 × 1.32 |
0.7 |
1.8 |
16.5 |
495 |
3 × 16 |
7 × 1.66 |
0.7 |
1.8 |
18.9 |
712 |
3 × 16 + 10 |
7×1.66 / 7×1.32 |
0.7/07 |
1.8 |
20.1 |
817 |
4 × 1.5 |
1.35 |
0.7 |
1.8 |
11.3 |
173 |
4 × 2.5 |
1.73 |
0.7 |
1.8 |
12.3 |
224 |
4 × 4 |
2.19 |
0.7 |
1.8 |
13.4 |
292 |
4 × 6 |
2.68 |
0.7 |
1.8 |
14.6 |
382 |
4 × 10 |
7 × 1.32 |
0.7 |
1.8 |
17.9 |
612 |
4 × 16 |
7 × 1.66 |
0.7 |
1.8 |
20.5 |
889 |
5 × 1.5 |
1.35 |
0.7 |
1.8 |
12.3 |
205 |
5 × 2.5 |
1.73 |
0.7 |
1.8 |
13.4 |
267 |
5 × 4 |
2.19 |
0.7 |
1.8 |
14.6 |
358 |
5 × 6 |
2.68 |
0.7 |
1.8 |
16 |
471 |
5 × 10 |
7 × 1.32 |
0.7 |
1.8 |
19.6 |
745 |
5 × 16 |
7 × 1.66 |
0.7 |
1.8 |
22.6 |
1066 |