Intrinsically safe cable is mainly used for intrinsically safe circuits of auto-control systems in chemical industry, especially petrochemical industry
|
 |
Intrinsically safe compensation cable for thermocouple
Type: 2X(St)Y1×2×1.5mm2,NiCr-Ni.
Standard: According to VDE standard.
Testing Voltage: 1 minute, AC 2000V, 150Hz
Core Insulation Layer: Specially processed PO, 0.6mm thick, 1.6mm external Φ.
Conductor Core Mark: (+)RED, (-)GREEN.
Shield: Lead foil taped covering + 0.34mm2 tinning copper ground lead.
Sheath: 1.6mm thick 70ºC blue fire resistant PVC.
External Diameter: 9.1mm
DC Loop Resistance (0-200ºC): 420±10%Ω/Km
Minimal insulation resistant (core-core/shield): 5000MΩ/Km
Maximal Capacitance: 120nF/Km
Standard Length: 500m
Minimal Installation Temperature: -10ºC
Environment Temperature: -50∼+70ºC
Minimal Bending Radius for fixed installation: 15×EDΦ
Intrinsically safe cable for current and signal transmission
Type: 2X(St)Y1×2×1.3mm2
Standard: According to VDE standard.
Working Voltage: 500V.
Testing Voltage: 1 minute, AC 2000V, 150Hz
Conductor Core: Electrolytic copper soft wire
Core Insulation Layer: Specially processed PO, 0.6mm thick, 2.7mm ED Φ.
Conductor Core Mark: WHITE, YELLOW
Shield: Lead foil taped covering + 0.34mm2 tinning copper ground lead.
Sheath: 1.6mm thick 70ºC blue fire resistant PVC.
External Diameter: 9.0±0.7mm
Maximal DC Loop Resistance (0∼200ºC): 30.4Ω/Km
Minimal insulation resistant (core-core/shield): 5000MΩ/Km
Maximal Capacitance: 110nF/Km
Standard Length: 500m or 1000m
Minimal Installation Temperature: -10ºC
Environment Temperature: -50∼+70ºC
Minimal Bending Radius for fixed installation: 15×EDΦ